Grounding methods for cable shielding layers

Release time: 2026-09-20


The durability of wires and cables should be evaluated based on two key factors: the intrinsic properties of the conductor itself, and the installation method. The installation method, in turn, encompasses the specific construction techniques employed. Cable shielding layers are typically made from non‑magnetic materials such as copper or aluminum and are very thin—far thinner than the skin depth of metallic materials at the operating frequency. Consequently, the shielding effectiveness does not primarily arise from the reflection or absorption of electric or magnetic fields by the metal itself, but rather from the grounding of the shield. The particular grounding configuration directly influences the shielding performance. With respect to grounding for electric and magnetic field shielding, options include ungrounded, single-point grounding, or two-point grounding.

 

So, under what circumstances should these grounding methods be used?

When a short-circuit current or a lightning current flows through the grounding grid, the potential difference between two points on the cable’s shield causes a current to circulate within the shield, which may lead to its burnout. Once such a current flows in the shield, it generates interference signals on each conductor. For relay protection and automatic devices—whose inputs and outputs are both exposed to high‑voltage or extra‑high‑voltage conditions in the switchyard—the primary concern is electromagnetic induction; moreover, since the circuits carrying the cable conductors are power circuits, the interference induced by the shield current is relatively minor. Consequently, the relevant regulations for relay protection and automatic devices stipulate that the shield should be grounded at both ends. For control cables, the shield is also grounded at both ends. The ability of the shield to reduce induced overvoltages stems mainly from the cancellation effect between the magnetic field generated by the shield current and the magnetic field produced by the interfering currents. Grounding the shield at both ends is preferred because, during short‑circuit or lightning currents, although the magnitude of these currents is large, their duration is very brief, making it unlikely that the shield will be burned out. By contrast, if the shield is grounded at only one end, no closed current loop is formed, resulting in significantly reduced overvoltage suppression and interference‑rejection capabilities, and thus failing to achieve effective shielding.

 

Corrective measures: First, ensure that cable shielding is properly grounded at both the switchyard and the control room, and that the shielding of communication cables is also reliably and correctly bonded to ground. Second, install dedicated copper grounding busbars for secondary equipment and secondary cables to minimize interference caused by ground potential differences. Third, employ dedicated opto‑electronic isolation for all discrete input and output contacts in the substation.

 

The induced current flowing in the shield is generated by the external electromagnetic field, and its primary function is to counteract interference from that field. Therefore, grounding both ends of a cable’s shield can effectively suppress electromagnetic induction. A shield that is not grounded provides no shielding against electric‑field interference, whereas shields grounded at one end or at both ends offer identical shielding performance for electric fields. When the shield is properly grounded, the electric field terminates on the shield and couples directly to earth. The metallic shield of a shielded cable provides electrostatic shielding: the strong electric field lines from the high‑voltage primary power source terminate on the metal shield, resulting in zero electric field strength inside and protecting the conductors within the shield from external strong electric‑field disturbances. From the perspective of electrostatic shielding, to ensure that the shield surface remains a fixed equipotential plane, one end of the shield should be grounded.