Wire and Cable Inspection Knowledge — Low-Temperature Wrapping Test
Release time: 2026-08-13
I. Purpose of Inspection
The low‑temperature winding test is an inspection method used to evaluate the cold‑resistance performance of wires and cables, determining whether these products can operate normally under severe cold conditions or other low‑temperature environments. For fixed installations, the product’s cold‑resistance requires that, when installed at the minimum permissible ambient temperature and within the minimum allowable bending radius, its insulation and jacket remain intact without cracking, and that it does not develop cracks during prolonged operation at low temperatures due to bending‑induced residual stresses or molecular‑structural forces. For products intended for mobile or semi‑mobile use, the requirement is that, at low temperatures, they withstand repeated mechanical stresses imposed by multiple bends at a relatively small bending radius without damage to the insulation and jacket—meaning that the insulation and jacket must retain a certain degree of flexibility and elasticity even under cold conditions. Accordingly, the purpose of the low‑temperature winding test is to verify whether the product’s low‑temperature bending performance meets the requirements specified in the relevant standards.
II. Scope of Application
1. This test is applicable to circular insulated conductors with an outer diameter of 12.5 mm or less, as well as to sector‑shaped insulated conductors that cannot be prepared into dumbbell‑shaped specimens.
2. This test is applicable to sheathed cables with an outer diameter of 12.5 mm or less and to flat cables with a short‑axis dimension of 20 mm or less.
III. Basis for Inspection
GB/T 2951.14—2008/IEC 60811-1-4:2001 and relevant product standards.
IV. Test Equipment and Instruments
Low-temperature chamber, low-temperature winding device.
V. Sampling and Specimen Preparation Equipment
1. Take two specimens of appropriate length from each test cable.
2. The outer jacket shall be removed from the low-temperature insulation winding specimen (if an outer jacket is present).
3. For the low-temperature winding test of the sheath, all protective layers on the sheath shall be removed.
VI. Test Procedure
1. Select the test temperature.
a. Polyvinyl chloride insulated cable 15±2℃
b. Rubber-insulated cable 35±2℃
c. or in accordance with the relevant standards.
2. Select the diameter of the test rod.
a. For round insulated cores and sheathed cables, the diameter of the test rod shall be 4 to 5 times the diameter of the specimen.
b. The diameter of the test rod for a fan-shaped specimen is 4 to 5 times the minor axis dimension.
c. The diameter of the test mandrel for flat flexible cords shall be 4 to 5 times the minor axis dimension of the specimen, with the minor axis perpendicular to the mandrel during winding.
3. Secure one end of the specimen to the winding apparatus. The equipment containing the specimen shall be placed in a low-temperature chamber at the specified temperature for no less than 16 hours, with the 16-hour cooling period including the time required for the cooling system to reach and maintain the set temperature.
4. If the test equipment has been pre‑cooled, the cooling time may be shortened provided that the specimens have reached the specified test temperature; however, the minimum cooling time shall not be less than 4 hours. If both the test equipment and the specimens have been cooled, each specimen shall remain mounted on the test equipment for an additional 1 hour to ensure adequate cooling.
|
Specimen outer diameter (mm) |
|
|
d ≤2.5 |
10 |
|
2.5 |
6 |
|
4.5 |
4 |
|
6.5 |
3 |
|
8.5 |
2 |
5. After the prescribed cooling period has elapsed, the test rod shall be rotated at a uniform rate of approximately one revolution every 5 seconds (see the table above for the number of revolutions), ensuring that the specimen is neatly wound onto the rod in a tight helical coil. If the specimen is sector‑shaped, its circular “back” shall be in contact with the test rod, after which the specimen shall be held on the rod until it returns to a temperature close to ambient.
VII. Evaluation of Test Results
After the prescribed test is completed, inspect the specimens remaining on the test rod. When examined with unaided or corrected vision—without the use of a magnifying glass—both insulating specimens shall show no cracks to be considered合格 (qualified).