Voltage Test Method for Wire and Cable Products
Release time: 2026-07-27
1. Test equipment
The power-frequency withstand voltage tester operates at a test‑voltage frequency of 49–61 Hz, with the measured voltage maintained within ±3% of the specified value. For low‑voltage cables, an adjustable transformer is typically used to generate the test voltage; for medium‑ and high‑voltage cables, a series resonant circuit may also be employed.
II. Sample Preparation
Specimen Cutting
For PVC‑insulated wires and cables, as well as rubber‑insulated cables, with a rated voltage of 750 V or less, the minimum length of test specimens for cable voltage tests is 10 m, while the minimum length for insulation core voltage tests is 5 m.
For routine tests of low-voltage power cables, the sample length for type tests is 10–15 m.
3. Test Procedure
Wiring method
The conductor is connected to high voltage, while the other conductors and the metal layer or water are grounded.
Pressurization method
The voltage should be started at a sufficiently low value—typically below 40% of the specified test voltage—and then increased gradually to ensure accurate readings on the measuring instrument. Once the voltage exceeds 75% of the test voltage, it may be raised at a rate of 2% per second to meet the requirements.
Voltage reduction method
The power supply may be disconnected only after the voltage has been reduced to below 40% of the specified test voltage.
4. Safety Precautions
(1) Operators of the dielectric withstand tester must wear rubber insulating gloves and stand on a rubber insulating mat to prevent high-voltage electric shock; the dielectric withstand tester must be reliably grounded.
(2) Prior to the start of the test, a functional check of the equipment shall be performed to ensure that the breakdown testing apparatus can be de-energized.
(3) During dielectric withstand testing, the instrument’s grounding terminal must be securely connected to the device under test; open-circuit conditions are strictly prohibited.
(4) If the test lamp or alarm of the withstand voltage tester is damaged, it must be replaced immediately to prevent misjudgments.
5. Test Record
(1) Specimen number, specimen specifications, and model;
(2) Test date, atmospheric conditions;
(3) The magnitude and duration of the applied voltage;
(4) Test results.