What are the differences among YJV, YJY, and VV cables?
Release time: 2026-05-08
Introduction
During the selection process for power cables, YJV 、 YJY 、 VV These are three commonly used cable models. While they look similar, they differ significantly in materials, performance, and application scenarios. Choosing the right cable not only ensures electrical safety but also enhances the system’s cost-effectiveness and reliability. This article will provide a detailed comparison of the differences among these three types.
I. Basic Definitions of Three Types of Cables
|
Model |
Full name |
Insulating material |
Sheath material |
|
YJV |
Copper-conductor cross-linked polyethylene-insulated PVC-sheathed power cable |
Cross-linked polyethylene ( Cross-Linked Polyethylene ) |
Polyvinyl chloride ( PVC ) |
|
YJY |
Copper-conductor cross-linked polyethylene-insulated, polyethylene-sheathed power cable |
Cross-linked polyethylene ( Cross-Linked Polyethylene ) |
Polyethylene ( PE ) |
|
VV |
Copper-conductor PVC-insulated, PVC-sheathed power cable |
Polyvinyl chloride ( PVC ) |
Polyvinyl chloride ( PVC ) |
As can be seen from the definition, YJV and YJY The insulation materials are the same; the difference lies in the jacket; and VV Both the cable’s insulation and jacket are made of polyvinyl chloride, making it a relatively early-generation product.
II. Core Performance Comparison
|
Performance Metrics |
YJV |
YJY |
VV |
|
Long-term permissible operating temperature of the conductor |
90 degrees Celsius |
90 degrees Celsius |
70 degrees Celsius |
|
Maximum temperature during a short circuit ( 5s Inside) |
250 degrees Celsius |
250 degrees Celsius |
160 degrees Celsius |
|
Minimum operating ambient temperature |
-15 degrees Celsius |
-40 degrees Celsius |
-15 degrees Celsius |
|
Release of harmful gases during combustion |
Contains (halogen) |
Halogen-free or low-smoke |
Contains (halogen) |
|
Environmental performance |
General |
Excellent |
General |
|
Price level |
Moderate |
Slightly higher than YJV |
Slightly below YJV |
III. Application Scenarios for Each Model
1. YJV Cable —— Mainstream Engineering Choices
YJV Cables are currently the most widely used type in power engineering projects. Their cross-linked polyethylene insulation boasts a high temperature rating and large current-carrying capacity, while the polyvinyl chloride sheath offers excellent mechanical strength at a moderate cost.
Applicable scenarios:
- Urban power grids, industrial parks
- Industrial and mining enterprises, power plants
- Outdoor buried and tray installation
2. YJY Cable —— An Eco-Friendly and Cold-Resistant Choice
YJY The cable features a polyethylene jacket and does not emit significant amounts of harmful gases during combustion, classified as “ Low-smoke, halogen-free ” Type cable. It also boasts excellent low-temperature resistance, making it suitable for harsh climatic conditions.
Applicable scenarios:
- Subways, train stations, hospitals, shopping malls, and other densely populated venues
- Scenarios with stringent security requirements, such as data centers and fire protection systems
- Cold regions ( -20 degrees Celsius The following) Outdoor installation
3. VV Cable —— Traditional models are being gradually replaced.
VV Cables were early, commonly used power cables, with conductors that permit a lower operating temperature ( 70 degrees Celsius ), under the same cross-section, the traffic is lower than YJV . Currently, its market share is gradually being eroded by YJV Replace.
Applicable scenarios:
- Temporary Electrical Engineering
- Upgrade of legacy equipment or projects (to ensure compatibility with the existing system)
- Applications with low requirements for temperature and current-carrying capacity
IV. How to Quickly Select the Right Model?
|
Usage Requirements |
Recommended Model |
|
For general industrial and civil engineering projects, cost-effectiveness is prioritized. |
YJV |
|
Indoor spaces, shopping malls, subways, and other venues with stringent environmental and safety requirements |
YJY |
|
Extreme cold regions ( -20 degrees Celsius The following) Outdoor installation |
YJY |
|
Temporary power usage or legacy projects with extreme cost sensitivity |
VV |
Conclusion
YJV 、 YJY 、 VV Each of the three cable types has its own characteristics; when selecting a cable, factors such as the operating environment, safety requirements, and budgetary constraints should be considered comprehensively. YJV It is currently the most mainstream choice. YJY It is more suitable for projects with stringent requirements for environmental protection and cold resistance, while VV Then gradually withdraw from the mainstream market.