On the Differences Between BVR Cable Conductors and Class 5 Conductors
Release time: 2025-12-02
With the development of the national economy, the application range of BVR wires is expanding continuously. Most domestic cable manufacturers are now capable of producing BVR wires, and currently, some domestic enterprises are engaged in their production. BVR When manufacturing wires, in order to reduce conductor consumption, the number of single-strand drawing operations, equipment downtime caused by frequent replacement of drawing dies, and the occupation of tooling fixtures, we adopt the Class 5 flexible conductor structure as specified in the national standard GB/T 3956-2008. The Class 5 flexible conductor structure is used for soft cables; BVR wires and soft cables employ the same type of conductor, significantly lowering production costs for enterprises. However, from the perspective of the national standard, this article briefly discusses whether the Class 5 conductor structure used in BVR wires meets the standard requirements. Any inaccuracies are welcome to be pointed out and corrected.
Currently, the standards applied to BVR wire products are specified in Part 2—“Wires and Cables for Fixed Wiring”—of the Ministry of Machinery Industry Standard JB/T 8734-2016, “Polyvinyl Chloride Insulated Wires and Cables and Flexible Cords Rated 450/750V and Below.” This standard sets strict requirements for the number of conductors and DC resistance of BVR cables. See Table 1 for details:
Table 1
|
Nominal cross-sectional area of conductor / mm 2 |
Stranded conductor Minimum number of roots |
20 ° Maximum resistance at time Ω/km |
|
2.5 |
19 |
7.41 |
|
4 |
19 |
4.61 |
|
6 |
19 |
3.08 |
|
10 |
49 |
1.83 |
|
16 |
49 |
1.15 |
|
25 |
98 |
0.727 |
|
35 |
133 |
0.524 |
|
50 |
133 |
0.387 |
|
70 |
189 |
0.268 |
The conductors used by domestic enterprises in the production of flexible cables are Class 5 stranded flexible conductors. The conductor structure shall comply with the national standard GB/T 3956-2008 “Conductors for Cables.” This standard specifies the diameter of individual strands and the DC resistance for Class 5 flexible conductors. For details, see Table 2.
Table 2
|
Nominal cross-sectional area of conductor / mm 2 |
Maximum single wire diameter in conductor/mm |
20 ° Maximum resistance at time Ω/km |
|
2.5 |
0.26 |
7.98 |
|
4 |
0.31 |
4.95 |
|
6 |
0.31 |
3.30 |
|
10 |
0.41 |
1.91 |
|
16 |
0.41 |
1.21 |
|
25 |
0.41 |
0.780 |
|
35 |
0.41 |
0.554 |
|
50 |
0.41 |
0.386 |
|
70 |
0.51 |
0.272 |
Based on the comparison of the two conductor structures mentioned above, their DC resistance requirements differ. As shown by the standard-specified values, the DC resistance of the conductor used in BVR wires is lower than that of the Class 5 flexible conductor. For details, see Table 3.
Table 3
|
Nominal cross-sectional area of conductor / mm 2 |
The maximum resistance of Class 5 conductor at 20°C is Ω/km. |
(BVR use) Maximum resistance at 20°C: Ω/km |
|
2.5 |
7.98 |
7.41 |
|
4 |
4.95 |
4.61 |
|
6 |
3.30 |
3.08 |
|
10 |
1.91 |
1.83 |
|
16 |
1.21 |
1.15 |
|
25 |
0.780 |
0.727 |
|
35 |
0.554 |
0.524 |
|
50 |
0.386 |
0.387 |
|
70 |
0.272 |
0.268 |
Conclusion: The conductors used in the production of BVR wires must comply with the requirements specified in JB/T 8734-2016, "Cables and Wires with Polyvinyl Chloride Insulation Rated at 450/750 V and Below," and may not be substituted with the Class 5 flexible conductor structure as defined in GB/T 3956-2008, "Conductors for Cables."